logo
Hoş geldiniz. ESTEL (GUANGDONG) TECHNOLOGY CO., LTD.
+8613752765943 / 86-0755 23592644

ET48300-A7E412 18kW PV + 12kW Rectifier 12U -48V Hybrid Telecom Power Platform

Temel Özellikler
Menşe Yeri: Çin
Marka Adı: ESTEL
Sertifikasyon: CE UL FCC
Ticaret Mülkleri
Minimum Sipariş Miktarı: 1 Takım
Fiyat: USD300-USD1000
Ödeme Koşulları: Banka havalesi, Western Union
Tedarik Yeteneği: 5000
Ürün Özetleri
ET48300-A7E412 18kW PV + 12kW Rectifier 12U -48V Hybrid Telecom Power Platform The ET48300-A7E412 is a 12U hybrid -48V DC power platform designed for telecom sites using both solar power and AC mains power. It integrates PV input, rectifier modules, battery distribution, load protection, surge ...

Ürün Detayları

Vurgulamak:

18kW PV telecom power system

,

12kW rectifier hybrid power platform

,

12U -48V telecom power system

Mains Configuration: 230/400Vac
Dc Output Currency: 83,4 ADC
Coolingmethod: Cebri Hava Soğutma / Doğal Konveksiyon
Protectionfeatures: Aşırı Gerilim, Aşırı Akım, Kısa Devre, Termal Koruma
Communication: RS485/SNMP
Customizable: Destek
Efficiency: T/T
Input Power: 380V, 3 fazlı
Power Distribution Panel: Özelleştirilmiş
Material: Sandviç yapısı çelik panel
Dc Output: 3 kol kompakt kırıcı
Input Current Harmonic: ≤3%(100% doğrusal olmayan yük)
Output Data: 24Vdc
Nominal Capacity: 50Ah
Input Frequency: 57-63 ve 47-53Hz
Ürün Açıklaması

ET48300-A7E412 18kW PV + 12kW Rectifier 12U -48V Hybrid Telecom Power Platform

 

The ET48300-A7E412 is a 12U hybrid -48V DC power platform designed for telecom sites using both solar power and AC mains power. It integrates PV input, rectifier modules, battery distribution, load protection, surge protection and intelligent monitoring in one 19-inch rack-mounted system.

 

This model is suitable for outdoor telecom cabinets, solar base stations, weak-grid sites, off-grid relay stations and battery backup power systems. The front-maintenance design, hot-swappable modules and clear distribution layout make installation, inspection and field replacement easier for telecom engineers.

 

The system supports 18kW solar input and 12kW rectifier capacity. Six 3kW PV/MPPT modules can work together with three 3kW rectifier modules, while one redundant slot improves system flexibility. The output range is -43V to -58VDC, with rated output at -53.5VDC.

 

Main Applications 18kW PV + 12kW Rectifier

Application Area

Description

Solar telecom base station

For hybrid PV and AC power supply

Outdoor telecom cabinet

Compact 12U rack-mounted installation

Weak-grid site

Reduces dependence on unstable grid power

Off-grid relay station

Supports solar charging and battery backup

Fiber access network

Provides stable -48VDC power distribution

Battery backup system

Protects critical communication loads

 

Technical Specifications 18kW PV + 12kW Rectifier

Item

Specification

Model

ET48300-A7E412

System Type

18kW PV + 12kW rectifier hybrid power platform

System Voltage

-48VDC telecom power system

DC Output Range

-43V to -58VDC

Rated DC Output

-53.5VDC

Total PV Capacity

18kW, 6 × 3kW

Rectifier Capacity

12kW, 3 × 3kW + 1 redundant slot

Installation

19-inch rack-mounted

Dimensions

482.6mm W × 350.6mm D × 12U H

Weight

≤40kg, without modules

Maintenance

Front maintenance

Module Design

Hot-swappable

Cabling Mode

Bottom inlet, top outlet

Shelf Cooling

Natural cooling

Protection Level

IP20

AC Distribution 18kW PV + 12kW Rectifier

Item

Specification

AC Input

Dual live wire + N, 220Vac

Input Voltage

L1-L2: 220V; L1-N: 110V; L2-N: 110V

Input Breaker

2 × 125A/2P, manual interlock

Frequency

45–65Hz

Rated Frequency

50Hz / 60Hz

AC SPD

20kA / 40kA, 8/20μs

AC Output

2 × 63A/1P, L1-N

Additional AC Output

3 × 32A/1P, L2-N

AC Socket

2 × 110V / 15A / NEMA 1-15

 

DC Distribution 18kW PV + 12kW Rectifier

Item

Specification

Battery Breakers

2 × 125A/1P

Load Breakers

1 × 63A/1P + 2 × 20A/1P + 6 × 10A/1P

Load Control

Secondary power-off supported

DC SPD

10kA, 8/20μs

Load Protection

Supports priority load distribution

 

Rectifier Module 18kW PV + 12kW Rectifier

Item

Specification

Input Voltage

85VAC to 300VAC

Rated Input

220VAC

Rated Output Power

3000W

Efficiency

≥96%

Power Factor

≥0.99 at 220Vac, 20%–100% load

Operating Temperature

-40°C to +75°C

Full-load Condition

Below 50°C

Dimensions

106.5mm W × 286mm D × 41.5mm H

Height

1U

Weight

≤2.0kg

Cooling

Forced air cooling

 

PV / MPPT Module 18kW PV + 12kW Rectifier

Item

Specification

PV Input Voltage

120Vdc to 420Vdc

Rated PV Input

340Vdc

PV Input Breaker

6 × 25A/2P

PV Input SPD

6 × 20kA / 40kA, 8/20μs

PV Module Input

120Vdc to 425Vdc

PV Module Power

3000W

PV Module Efficiency

96%

MPPT Accuracy

≥0.99

Operating Temperature

-40°C to +75°C

Full-load Condition

Below 50°C

Dimensions

106.4mm W × 285mm D × 41.5mm H

Height

1U

Weight

≤2kg

Cooling

Forced air cooling

 

Monitoring and Communication 18kW PV + 12kW Rectifier

Item

Specification

Display

LCD

Communication

RS485, SNMP

AI Input

3 channels

Temperature Sensors

2 battery sensors + 1 ambient sensor

DI Input

6 channels

Alarm Output

6 dry-contact outputs

Remote Monitoring

Supported

 

ET48300-A7E412 18kW PV + 12kW Rectifier 12U -48V Hybrid Telecom Power Platform 0

ET48300-A7E412 18kW PV + 12kW Rectifier 12U -48V Hybrid Telecom Power Platform 1

ET48300-A7E412 18kW PV + 12kW Rectifier 12U -48V Hybrid Telecom Power Platform 2

 

 

Environmental Conditions 18kW PV + 12kW Rectifier

Item

Specification

System Operating Temperature

-40°C to +70°C

Full-load Condition

Below 50°C

Storage Temperature

-40°C to +75°C

Operating Humidity

5%–95%

Altitude

0–3000m

Application Environment

Telecom cabinet, solar site, hybrid power station

İLGİLİ ÜRÜNLER
  • 28U Düzeltme Sistemi ile Entegre Dış Güç Kabinesi UPS Pil enerji depolama kabı

    Düzeltme Sistemiyle 28U Entegre Dış Güç Kabinesi UPS Pil Enerji Depolama 1Kısa bir tanıtım: Açık hava telekom dolapları genellikle telekom ekipmanlarının korunmasını ve işlevselliğini sağlamak için çeşitli özelliklere sahiptir. Hava Duruma Dayanıklı Tasarım: Açık hava dolapları, yağmur, kar, aşırı ...
  • Dış Mekan Güç Kabini, Su Sensörlü / Kapı Sensörlü Dış Mekan Telekom Kabini

    Dış Güç Kabini, Su Sensörlü Dış Mekan Telekom Kabini / Kapı Sensörü 1. Açıklama Dolap tek bölmeli dolaptır.Kabin soğutması, ekipmanların hizmet ömrünü çok daha uzun ve performanslarını daha istikrarlı hale getirmek için ekipmanların normal olarak sabit sıcaklık aralığında çalışmasını sağlamak için ...
  • Jeneratör Soketli Sıcaklık Kontrolü Dış Telekom Kabini IP55 Giriş Koruması

    Sıcaklık Kontrolü Dış Güç Kabini / Jeneratör Soketli Dış Telekom Kabini 1. Özellikler (1) Teknik Parametreler Giriş Koruması: IP55 B Sınıfı Yıldırım Geçirmez: Nominal: 60KA, Maks.: 100KA Sıcaklık: Çalışma Sıcaklığı: -40°C ~ +55°C Depolama Sıcaklığı: -50°C ~ + 70°C Taşıma Sıcaklığı: -50°C ~ +70°C Bağ...
  • Emerson Doğrultucu / Akü Dış Mekan Güç Kabini Sandviç Yapı Paneli IP55

    Emerson Doğrultucu ve Batarya ile Sandviç Yapı Paneli Dış Mekan Güç Kaynağı Kabini 1 Ürün Açıklaması 1.1 Dış görünüş Kabin montajı yapıldıktan sonra Şekil 1 ve Şekil 2'de gösterildiği gibi Şekil 1 Şekil 2 1.2 Kabin konfigürasyonu Bu projenin dış mekan entegre kabin konfigürasyonu aşağıdaki gibidir: ...

Soru Gönder